Wire Gauge Calculator (Free Tool, 2026)

What size wire do you need? This free wire gauge calculator finds the minimum AWG wire and breaker size for any household circuit based on the load, voltage, distance and cable type, and checks voltage drop so long runs stay safe and efficient.

Wire Gauge & Breaker Size Calculator

Pick the right AWG wire and breaker for any household circuit, including voltage drop.

Common circuit
Voltage
Load
One-way distance to panel (ft)
Conductor
Cable type
Max voltage drop
Use at least12 AWGcopper
Breaker size20 A
Design current15 A
Wire ampacity20 A
Voltage drop0%
GaugeAmpacityV dropOK?

Based on NEC Table 310.16 ampacities (NM-B at the 60°C column, THHN at 75°C), the small-conductor limits in NEC 240.4(D) and Chapter 9 resistance values, at ~30°C with no more than 3 current-carrying conductors. For planning only. Local codes, appliance instructions and derating can require larger wire. Have a licensed electrician do the work.

Embed This Wire Gauge Calculator on Your Site

Run a home improvement, smart home, contractor or real estate site? Add this free tool to any page. Copy the code below and paste it into an HTML block. It’s free, mobile-friendly and updates automatically.

Please keep the credit link below the tool. WordPress users: add a “Custom HTML” block and paste the code.

How to Use the Wire Gauge Calculator

  1. Pick a common circuit like a dryer, water heater or EV charger, or enter your own load in amps or watts.
  2. Set the voltage (120V for most outlets and lights, 240V for big appliances).
  3. Tick “continuous” if the load runs for three hours or more, such as heaters and EV chargers.
  4. Enter the one-way distance from the panel to the device.
  5. Choose copper or aluminum and the cable type, then read the minimum wire gauge, breaker size and voltage drop.

Wire Size and Breaker Chart (Copper)

BreakerNM-B cable (60°C)THHN in conduit (75°C)Typical use
15 A14 AWG14 AWGLighting, bedroom outlets
20 A12 AWG12 AWGKitchen, bath and garage outlets
30 A10 AWG10 AWGDryer, water heater
40 A8 AWG8 AWGElectric range, cooktop
50 A6 AWG8 AWGRange, EV charger (40 A)
60 A4 AWG6 AWGEV charger (48 A), sub-panel
100 A—3 AWGSub-panel feeder

Values follow NEC Table 310.16 and the small-conductor rule in 240.4(D) at normal temperatures. Hot attics, bundled cables and more than three current-carrying wires in a conduit all require larger wire. See the NFPA 70 (NEC) for the full rules.

Voltage Drop Formula

Voltage drop = 2 × one-way length (ft) × current (A) × resistance (Ω per 1,000 ft) ÷ 1,000. Divide by the circuit voltage to get a percentage. For example, 15 A on 14 AWG copper over 50 feet at 120V drops about 3.8%, so the calculator bumps it to 12 AWG (about 2.4%).

Continuous Loads and the 125% Rule

Loads that run for three hours or more, like EV chargers, baseboard heaters and water heaters, must be sized at 125% of their current. A 48 A EV charger needs a circuit rated for 60 A. Always follow the appliance’s installation manual, which may ask for more.

Safety First

  • Never put a bigger breaker on existing wire. The breaker protects the wire, not the appliance.
  • Most areas require permits for new circuits, and many require a licensed electrician.
  • Turn off the breaker and test with a non-contact tester before touching any wiring. The Electrical Safety Foundation has good home safety guides.

Planning bigger projects? See what an EV costs to charge with our EV Charging Cost Calculator, size a backup system with the Generator Size Calculator or Home Battery Backup Calculator, and check heater sizing with the Heater Size Calculator.

Frequently Asked Questions

What size wire do I need for a 20 amp breaker?

For copper, 12 AWG is the minimum for a 20 amp circuit. On long runs (roughly 70 feet or more at full load on 120V) you may need 10 AWG to keep voltage drop under 3%.

What gauge wire for a 30 amp breaker?

Use 10 AWG copper for a 30 amp circuit, such as a typical electric dryer or a 4,500 W water heater. Aluminum needs to be larger, usually 8 AWG.

What size wire for a 50 amp circuit?

With copper THHN in conduit and 75°C terminals, 8 AWG is rated 50 A. With NM-B (Romex), which uses the 60°C column, you need 6 AWG copper.

What wire and breaker do I need for a 48 amp EV charger?

A 48 A charger is a continuous load, so the circuit is sized at 125%: a 60 A breaker with 6 AWG copper THHN in conduit, or as the charger’s installation manual requires.

Why does voltage drop matter?

Long or thin wires lose voltage as heat. Too much drop makes motors run hot, lights dim and chargers slow down. Keeping drop under 3% on branch circuits is a common design target.

Can I use aluminum wire in my house?

Aluminum is common and fine for large feeders and service wires when installed correctly. For small branch circuits, copper is usually preferred because aluminum needs special AL-rated devices and careful terminations.